Foundation Fieldbus Universal Bridge DFI302
DFI302
Foundation Fieldbus Universal Bridge

The DFI302 is a powerful multifunction hardware component integral to the modular SYSTEM302 that includes all the best-of-breed hardware and software you need to manage, monitor, control, maintain and operate your plant. The DFI302 throughout the plant is completely self contained and performs most of the functions required by a system and very few additional components are therefore required.

  • Integral part of SYSTEM302
  • Single integrated unit of interface, linking device, bridge, controller, gateway, Fieldbus power supply and distributed I/O subsystem.
  • Tight integration with intelligent devices and software from multiple manufacturers due to use of open standards as FOUNDATIONTM Fieldbus and OPC.
  • Connects to existing equipment through conventional I/O and Modbus communication.
  • Full redundancy and fault isolation for high safety and uninterrupted operation
  • Leanest and most cost effective architecture.
  • High information throughput from plant floor throughout the enterprise.

Some Characteristics:

Ambient Conditions 
Operating
0 to 60 ?C (32 to 140 ?F) , 20-90% RH non-condensing.
Storage
-20 to 80 ?C (-4 to 176 ?F) , 20-90% RH non-condensing.
Physical Dimensions
One Backplane Segment     (4 modules)
163 x 149 x 138 mm (max)
Multiple (N) Backplane segments
N * 163 x 149 x 138 mm (max)
Controller
Type
32-bit RISC.
Sustained Performance
50 MIPS
Memory for Code
2 MB, 32-bit Flash Memory (Upgradable firmware)
Memory for Data
2MB, 32-bit NVRAM ( Data and configuration retention)
Fieldbus interface
  • Number of Ports: 4, independent with DMA
  • Physical Layer Standard: ISA-S50.02-1992
  • Baud Rate: 31.25 kbps (H1)
  • MAU Type: Passive (not bus powered)
  • Intrinsic Safety: NOT compliant
  • Isolation: 500 Vac (each channel)
Operation Voltage / Currente
?5 V ?5 % / 1.0 A (typical)
Connector Ethernet
RJ-45
Connector EIA-232
RJ-12
Power Supply for Backplane
Input
90-260 Vac
Output
5 V @ 3 A, 24 V @ 0.3 A
Maximum consumption
35 VA
Power Supply for Fieldbus
Input AC
90-260 Vac at 47 to 440 Hz
Input DC
127-367 Vdc
Maximum consumption
45 Watts
Output Voltage
24 Vdc ? 1 % for load 0 to full load voltage between 90-260 Vac
Output Current
0-1.5 A
Ripple
20 mV peak to peak
Alarm Output
1A, 30 Vdc SPST, Fail close.
Isolation
  • Between Output and Enclosure Ground: 500 Vrms
  • Between Input and Output: 3000 Vrms
Power Supply Impedance for Fieldbus
Input
24-32 Vdc ?10 %
Output Current
340 mA (max)
Output Overcurrent
Limited in 500 mA
Input Fuse
2.5 A