Vaisala CARBOCAP Carbon Dioxide Module GMM112
|
Compact OEM module for demand-controlled ventilation and other CO2 measurement.
- Compact OEM module for demand-controlled ventilation and other CO2 measurement applications
- Incorporates the Vaisala CARBOCAP® Sensor - the silicon-based NDIR sensor with unique internal referencing
- Advanced, single-beam, dual wavelength measurement with no moving parts
- Excellent long-term stability
|
Performance
|
|
CO2 measurement range |
0 … 2000 ppm, 0 … 5000 ppm, 0...10000 ppm |
|
Accuracy (including repeatability, non-linearity and calibration uncertainty) |
± (2 % of range + 2 % of reading) |
|
Long-term stability |
±5% of range/5 years |
|
Response time T90 |
1 min |
|
Temperature dependence, typical |
-0.35 % of reading / °C |
|
Pressure dependence, typical |
+0.15 % of reading/ hPa |
|
Warm-up time |
1 min, 10 min for full specification |
|
Product lifetime
|
> 10 years
|
Operating environment
|
|
Temperature
Humidity
Pressure
Electromagnetic compatibility
|
-5 ... +45 °C (23 … 113 °F)
0 ... 85 % RH
700 … 1200 hPa
EN61326-1. Generic Environment
|
Inputs and outputs
|
|
Operating voltage
Power consumption
Outputs
|
24 V (±20 %) AC/DC
<2 W
4 … 20 mA, 0 … 10 V, RS-485, 2-wire, non-isolated
|
|
|
To request more information, please fill the form below.
|
|
|
ITS Instruments
Under Construction..
Click here to continue.
|