Home | About Us | Products | Services | Careers | Contact Us | Resources | Testimonials
 
Torbar
Tribar - TOTAL METER PACKAGE
Mass Tribar
 
ITS Instruments   Under Construction..

  Click here to continue.
COMPENSATED MASS FLOWMETER
COMPENSATED MASS FLOWMETER
TOTAL METER PACKAGE

The MASS TRIBAR measures pressure, temperature AND Differential Pressure directly FROM the inserted TORBAR PRIMARY element AND computes compensated mass flow within the integral multivariable transmitter.

The MASS TRIBAR IS ideal FOR the mass flow measurement OF liquids AND gases. It IS also suitable FOR measurement OF saturated steam flow WITH the transmitter mounted vertically below the pipeline axis (see APPLICATION LIMITATION note below).

The MASS TRIBAR concept provides several direct advantages.

  • AVERAGED FLOW PROFILE MEASUREMENT
  • SIMPLE INSTALLATION
  • COMPACT INTEGRAL CONSTRUCTION
  • RTD EASILY REMOVABLE FOR MAINTAINANCE
  • REDUCED TRANSMISSION LAGS
  • LOW PRESSURE LOSS
  • SINGLE SOURCING
  • COMPETITIVE PRICING
SPECIFICATIONS
  • Accuracy ?1% flow ?0.1% OF calibrated span
  • Repeatability OF measurement 0.2%
  • Flow range turndown 5:1
  • Maximum pressure 100 Bar
  • Maximum temperature AT sensor 200?C
  • Minimum temperature AT sensor -40?C
  • Ambient temperature range -40?C/+85?C
  • System 2 wire (DC 11V - 45V) (EXTERNAL power supply required)
  • OUTPUT: 2 wire 4 - 20mA linear TO mass flow
  • Digital Hart Protocol available TO host which conforms TO the Hart Protocol
  • Pressure, temperature AND DP variables ARE available through Hart
  • Protection: IP67. EEXia11C T4/t5/t6
  • Wetted Parts: 316L Stainless Steel
  • Pipe Sizes 100mm TO 5000mm
  • Differential pressure ranges 0-6.2 mBAR TO 0-620 mBAR 24.8 mBAR TO 0-2060 mBAR
  • Stability 0.1% URL FOR 12 months
  • FOR ambient temperature effects AND ambient pressure effects, refer TO relevant transmitter details
INSTALLATION & LOCATION

FOR detailed information about the transmitter, refer TO transmitter specification sheet which IS available ON request.

APPLICATION LIMITATION

FOR steam flow AND other applications which fall outside the above specifications, the transmitter AND manifold should be mounted remotely. Please contact factory OR agent FOR details.