H1 Foundation Fieldbus & Profibus PA Repeater - DF 48

DF48
H1 Foundation Fieldbus & Profibus PA Repeater

The DF48 essentially works by taking an incoming signal from one network, "cleaning" and boosting the signal that is then transmitted on to another network segments. The DF48 performs this function in a bi-directional fashion to support this feature of Fieldbus.

Some Characteristics:

Power Supply Input 
Rated Input Voltage: 24 VDC ? 5 %
Rated Input Power: 3 W
Power Supply 
Maximum Voltage available at the barrier terminals at maximum current: 14 VDC
Maximum current: 100 mA at 14V
Short Circuit Electronic Protection:140 mA
Safety Parameters Hazardous
Area
45 Open Circuit Voltage (Voc):15 VDC and Power: 1887 mW
Short Circuit Current (Isc): 221,7 mA, Is=125,8 mA at 15V
Max. Allowed Capacitance: Refer to FISCO standard
Max. Allowed Inductance: Refer to FISCO standard
Internal Dissipation
Dissipation 3W maximum at 24V input, nominal Conditions
Cable Length Parameters*
15 Ohm/km =0,1 mH/km =80 nF/km =
Digital Signal Transmission
Compatible with 31.25kbit/sec Fieldbus systems
Fuse
Safe area Power Supply: 400mA
Hazardous area:160mA
Safe Area Fieldbus: 100mA
Terminals 
Accommodate conductors up to 2.5 mm2 (12AWG)
Isolation
2500V galvanic isolation between input, output, and power supply terminals. Tested at 1500Vrms minimum between hazardous and safe area terminals.
Ambient Temperature
-20? to + 60?C (Continuous operation)
-40? to + 80?C (storage/ off line)
Humidity 
-5% to 95% relative humidity
Marking
Ex II (1)G [Eex ia] IIB/IIC
Ex I M2 [Eex ia]
DF47 I.S. Barrier: It should be physically located in a safe area.