RP302 H1 Fieldbus Repeater
As cable lengths increase control signals deteriorate and can become unreadable by devices on the network. Signal repeaters can be used to avoid deterioration in large networks or over long network cable runs.
The RP302 takes an incoming signal from one network segment,"cleans" it for errors, and re-transmits the signal at full strength to another network segment, maintaining signal quality and message integrity. throughout all network segments. The RP302 performs this function in a bi-directional fashion to support Fieldbus Networks. It is fully compliant with the IEC1158-2/ISAS50.02 physical layer definition and specifications for Foundation Fieldbus and PROFIBUS.
An H1 bus topology Fieldbus network with DC power can support a network segment cable length of up to 1900 meters. Up to 4 repeaters may be used in series, providing for the total cable length of any particular network trunk or spur to be increased up to 5 times the cable length of one segment. This allows for a Fieldbus device to be located up to 9.5 Km (5.9 miles) away from a control room.
- 1500 VAC Isolation between networks
- Very Low DC leakage at repeater inputs
- Each unit can extend the Fieldbus network length up to 1900 meters
- Includes selectable bus terminators on both network sides
- 8 bit preamble can use 4 repeaters; 16 bit preamble can use 8 repeaters in series
- Accommodate conductors up to 2.5mm2 (12 AWG)
- Fast snap-on DIN mounting rail assembly
- Conforms to IEC 61158-2, 31.25 Kbit/s standard for Foundation Fieldbus and PROFIBUS
Some Characteristics:
Input |
Voltage: 24 Vdc ?5% Current (max.): 30 mA at 24 Vdc |
Internal Dissipation |
0.72W max at 24V input |
Digital Signal Transmission |
31.25 kbit/sec fieldbus systems |
Terminals |
Accomodate conductors up to 4mm? (12AWG) |
Ambient Temperature Limits |
-20 to 60 ?C (-4 to 140 ?F) |
Ambient Humidity Limits |
5-95% RH |
Power Supply |
250 mA |
Fieldbus Inputs |
100 mA |
Mounting |
Fast snap-on assembly on DIN mounting Rail |
|