DFI302
Foundation Fieldbus Universal Bridge
The DFI302 is a powerful multifunction hardware component integral to the modular SYSTEM302 that includes all the best-of-breed hardware and software you need to manage, monitor, control, maintain and operate your plant. The DFI302 throughout the plant is completely self contained and performs most of the functions required by a system and very few additional components are therefore required.
- Integral part of SYSTEM302
- Single integrated unit of interface, linking device, bridge, controller, gateway, Fieldbus power supply and distributed I/O subsystem.
- Tight integration with intelligent devices and software from multiple manufacturers due to use of open standards as FOUNDATIONTM Fieldbus and OPC.
- Connects to existing equipment through conventional I/O and Modbus communication.
- Full redundancy and fault isolation for high safety and uninterrupted operation
- Leanest and most cost effective architecture.
- High information throughput from plant floor throughout the enterprise.
Some Characteristics:
Ambient Conditions
|
Operating
|
0 to 60 ?C (32 to 140 ?F) , 20-90% RH non-condensing.
|
Storage
|
-20 to 80 ?C (-4 to 176 ?F) , 20-90% RH non-condensing.
|
Physical Dimensions
|
One Backplane Segment (4 modules)
|
163 x 149 x 138 mm (max)
|
Multiple (N) Backplane segments
|
N * 163 x 149 x 138 mm (max)
|
|
Type
|
32-bit RISC.
|
Sustained Performance
|
50 MIPS
|
Memory for Code
|
2 MB, 32-bit Flash Memory (Upgradable firmware)
|
Memory for Data
|
2MB, 32-bit NVRAM ( Data and configuration retention)
|
Fieldbus interface
|
- Number of Ports: 4, independent with DMA
- Physical Layer Standard: ISA-S50.02-1992
- Baud Rate: 31.25 kbps (H1)
- MAU Type: Passive (not bus powered)
- Intrinsic Safety: NOT compliant
- Isolation: 500 Vac (each channel)
|
Operation Voltage / Currente
|
?5 V ?5 % / 1.0 A (typical)
|
Connector Ethernet
|
RJ-45
|
Connector EIA-232
|
RJ-12
|
Power Supply for Backplane
|
Input
|
90-260 Vac
|
Output
|
5 V @ 3 A, 24 V @ 0.3 A
|
Maximum consumption
|
35 VA
|
Power Supply for Fieldbus
|
Input AC
|
90-260 Vac at 47 to 440 Hz
|
Input DC
|
127-367 Vdc
|
Maximum consumption
|
45 Watts
|
Output Voltage
|
24 Vdc ? 1 % for load 0 to full load voltage between 90-260 Vac
|
Output Current
|
0-1.5 A
|
Ripple
|
20 mV peak to peak
|
Alarm Output
|
1A, 30 Vdc SPST, Fail close.
|
Isolation
|
- Between Output and Enclosure Ground: 500 Vrms
- Between Input and Output: 3000 Vrms
|
Power Supply Impedance for Fieldbus
|
Input
|
24-32 Vdc ?10 %
|
Output Current
|
340 mA (max)
|
Output Overcurrent
|
Limited in 500 mA
|
Input Fuse
|
2.5 A
|
|