H1 Intrinsically Safe Barrier And Fieldbus Repeater SB312
SB312 - LP
FISCO Intrinsically Safe Fieldbus / Profibus Barrier and Repeater

The SB312-LP uses Intrinsically Safe (I.S.) technology to completely isolate the control network on the hazardous side of the barrier. It supplies up to 80mA to field devices located in the hazardous area in accordance with the FISCO model.

The incorporated repeater (operating in compliance with IEC 1158-2 specifications at 31.25 Kbits/s) cleans and boosts the incoming communication signal, transmitting it to instruments inside the hazardous environment without compromising the safety
requirements of explosion proof wiring.

The networks on the hazardous and safe sides of the SB312-LP are completely independent of each other.

The SB312-LP also incorporates bus termination for the hazardous network in its design so that only one far terminator is required and up to a 2.5 mm2 (12 AWG) conductor can be used.

Features

  • H1 Isolated Barrier and I.S. Power Supply
  • Built-in H1 Fieldbus Signal Repeater
  • Bus termination on Hazardous side
  • Provides up to 80mA at 14V to the Hazardous Network for field devices
  • Can be installed in safe area (Div. 2/Zone 2 or Div. 1/Zone 1)
  • Conforms to IEC 1158-2, 31.25 Kbit/s standard for Foundation Fieldbus and PROFIBUS
  • Complies with FISCO I.S. model
  • FM & CENELEC Intrinsic Safety standards certified
  • Based on PTB Report W-53, Investigations into Intrinsic Safety of Fieldbus Systems

Some Characteristics:

Power Supply Input
Rated Input Voltage: 24 VDC ? 5 %
Power Supply
Maximum Voltage available at the barrier terminals at maximum
Maximum current: 80 mA @ 14V
Short Circuit Electronic Protection: Trigger @ 100 mA
Steady State @ 45 mA
Safety Parameters
(Hazardous Area)
Open Circuit Voltage (Voc):15 VDC and Power: 1887 mW
Short Circuit Current (Isc): 221.7 mA, Is=125.8 mA at 15V
Max. Allowed Capacitance: Refer to FISCO standard
Max. Allowed Inductance: Refer to FISCO standard
Internal Dissipation
3W maximum at 24V input, nominal Conditions
Cable Length Parameters*
15 Ohm/km =0,1 mH/km =80 nF/km =
Digital Signal Transmission
Compatible with 31.25kbit/sec Fieldbus systems
Fuse
Safe area Power Supply: 400mA
Hazardous area: 125mA
Safe Area Fieldbus: 100mA
Terminals
Accommodate conductors up to 2.5 mm2 (12AWG)
Isolation
2500V galvanic isolation between input, output, and power supply terminals. Tested at 1500Vrms minimum between hazardous and safe area terminals.
Ambient Temperature
-20? to + 60?C (Continuous operation)
-40? to + 80?C (storage - off line)
Humidity
-5% to 95% relative humidity
Marking
Ex II (1)G [Eex ia] IIB/IIC
Ex I M2 [Eex ia] I