Output
|
Two-wire, 4-20 mA with superimposed digital communication. (Bell 202 - HART Protocol)
|
Output Action
|
Direct or Reverse
|
Accuracy
|
Linearity, hysteresis and repeatability
|
Configuration
|
Using local adjustment magnetic tool or through digital communication using HART protocol
|
Actual Position Sensing
|
Magnet (Non-contact) via Hall effect
|
Indication
|
Optional LCD indicator
|
Material
|
Injected low copper aluminum with polyester painting or 316 stainless steel housing
|
Process Temperature Limits
|
Ambient: -40 to 85 ?C (-40 to 185 ?F)
Process: -40 to100 ?C (-40 to 212 ?F)
|
Ambient Humidity Limits
|
0 to100 % RH
|
Hazardous Area Certification
|
Explosion proof, weather proof and intrinsically safe
|
Weight
|
Nominal: 0.80 kg;
Digital display adds: 0.13 kg;
Mountif bracket adds: 0.6 kg.
|