Home | About Us | Products | Services | Careers | Contact Us | Resources | Testimonials
 
Differential Pressure, Flow, Absolute Pressure,Gage Pressure& Level Transmitters
Density / Concentration Transmitters
Temperature Transmitters
Position Transmitters
Valve Positioners
Signal Converters
Safety Barriers
Repeaters
Power Supply Subsystems
Interfaces
Isolator
Foundation Fieldbus Discrete I/O Devices
Controllers
Linking Device and Bridges
Manifold Valves
Measurement Systems
Fieldbus Network Analyzer
Didactic Pilot Plant
Configuration Software
Accessories
Actuators
Asset Management
 
ITS Instruments   Under Construction..

  Click here to continue.
Foundation Fieldbus Remote I/O DC302
DC302
Foundation Fieldbus Remote I/O

The DC302 Fieldbus Remote I/O makes the integration of Fieldbus and conventional I/O easy. It is a single integrated easy to use piece of equipment including power, control, networking and I/O under one compact device requiring less panel space than other solutions. The DC302 is an integral part of SYSTEM 302 but also integrates into other systems supporting Foundation Fieldbus.

 

Some Characteristics:

Communication
FOUNDATION Fieldbus on 31.25 kbit/s voltage mode according to IEC 61158-2
Power Consumption
Quiescent 12 mA
Output Impedance
Non-intrinsic safety from 7.8 kHz - 39 kHz should be greater or equal to 3 k. Intrinsic safety output impedance (assuming an IS barrier in the powersupply) from 7.8 kHz 39 kHz should be greater or equal to 400
Function Blocks
Up to 20 Dynamically Instantiable Function Blocks.

The Function Blocks available allow simple and complex control strategies to be placed inside the field device, making the field device and integral part of the control system. In order to fully benefit from the Function Blocks in the device a True Foundation Fieldbus system is recommended.
 
Temperature Limits
Operation: -40 to 85?C (-40 to 185 ?F)
Storage: -40 to 110?C (-40 to 230 ?F)
Housing
Housing Shell and Base: Polycarbonate, 10% Glass Filled
Terminals:
Pressure Plate /Terminal Screws: Zinc Plated, Yellow Chromated Steel
Temperature rating:
110?C (230 ?F) UL94VO
Protection:
it has IP20 rating (finger protected) and meets VBG4 and other European accident prevention requirements. It can optionally be supplied preinstalled in an enclosure ready for field mounting
Power Supply
Bus powered: 9-32 Vdc
Mounting
Using DIN rail (TS35-DIN EN 50022 or TS32-DIN EN50035 or TS15-DIN EN50045

 

Inputs

Architecture
Number of Inputs: 16
Isolation
Optical Isolation up to: 5000 Vac
External Power 
Voltage Source for Inputs: 18 - 30 Vdc
Typical Consumption per group 120 mA (all inputs ON)
Power indicator: Green LED
Inputs
ON State Level (True Logic): 15 - 30 Vdc
OFF State Level (False Logic): 0 - 5 Vdc
Typical Impedance: 3k9 W
Status display: Red LED
Switching Information 
Time from "0" to "1": 30 us
Time from "1" to "0": 50 us
Wiring
One wire: 14 AWG (2 mm 2 )
Two wires: 20 AWG (0.5 mm 2 )

 

Outputs

Architecture
Number of Outputs: 8
Isolation
Optical Isolation up to: 5000 Vac
External Power
Voltage Source for Outputs: 20 - 30 Vdc
Maximum Consumption  35 mA
Power indicator: Green LED
Outputs 
Maximum Switched Voltage: 30 Vdc
Maximum Saturation Voltage: 0.55 V @ 0.5 A
Maximum Current per Output: 0.5 A
Status Display: Red LED
Indicator Logic: ON when the transistor is on
Maximum Leakage Current: 100 uA @ 35 Vdc
Maximum Power Consumption for Bulbs: 15 W
Independent
Protection per Output
 
Thermal Shutdown: 165 o C
Thermal Hysteresis: 15 o C
Over-Current Protection: 1.3 A @ 25 Vdc maximum
Clamp Diode
Switching Information 
Time from "0" to "1": 250 us
Time from "1" to "0": 3 us
Wiring
One wire: 14 AWG (2 mm 2 )
Two wires: 20 AWG (0.5 mm 2 )

To request more information, please fill the form below.